En - 36 – HT instruments SOLAR300N User Manual

Page 38

Advertising
background image

SOLAR300 - SOLAR300N

EN - 36

12/09/2006 – 16:55:10

VOLTAGE HARMONICS

h[%] Phase

1

Thd% 6.5

DC

0.0

h1

100.0

h2

0.0

h3

1.8

h4 0.0

HARM I

GRAPHIC HARM PAG

12/09/2006 – 16:55:10

VOLTAGE HARMONICS

h[V] Phase

1

Thd% 6.5

DC

0.0

h1

228.6

h2

0.0

h3

4.2

h4 0.0

HARM I

GRAPHIC HARM PAG

Fig. 75: Harmonic analysis voltage in percentage/absolute for Single phase system

12/09/2006 – 16:55:10

CURRENT HARMONICS

h[%] Phase

1

Thd% 35.5

DC

0.0

h1

100.0

h2

0.0

h3

45.3

h4 0.0

HARM V GRAPHIC HARM PAG

12/09/2006 – 16:55:10

CURRENT HARMONICS

h[A] Phase

1

Thd% 35.5

DC

0.0

h1

199.7

h2

0.0

h3

90.6

h4 0.0

HARM V

GRAPHIC HARM PAG

Fig. 76: Harmonic analysis current in percentage/absolute for Single phase system

Press F3 key to back to graphical screens and F2 key to change voltages’ or currents’
screens. Press F4 key or the up and down arrows (or touch the “HARM PAG” at display)
to show the screens relative to other harmonics orders up to 49

st

.

 Harmonics values of single V1, V2, V3 voltages and neutral voltage Vn and single

currents I1, I2, I3 and neutral current In (for three phase 4-wire system) with THD%
values both with histogram graphics and with numerical values in percentage or
absolute value depending on the desired settings. These values are shown in four
pages selectable by pressing cyclically the F1 key (or touch the “PAGE” at display). As
an example, the situation relative to L1 phase for voltage and current on 4-wire
systems is shown in the next pictures:

12/09/2006 – 16:55:10

PHASE1 HARM VOLTAGE – Pag 2/5

h 01

Fs 100%
V1h

100.0 %

Thd

6.5 %

PAGE

HARM I

TABLE

HARM PAG

12/09/2006 – 16:55:10

PHASE1 HARM VOLTAGE – Pag 2/5

h 01

Fs

400.0V

V1h

228.6V

Thd

6.5 %

PAGE

HARM I

TABLE

HARM PAG

Fig. 77: Harmonic analysis voltage V1 in percentage/absolute values for 4-wire system



Advertising