Electrical System

9.70

G10-55A & G12-55A AccuPlace

RIGHT
STABILIZER
DOWN VALVE –
SHORT TO
GROUND

33230 Loss of current feedback on

UGM pin J3-6 while driving
coil via UGM pin J2-19.

N

Check for continuity through this circuit.

Inspect wiring for physical damage.

RIGHT
STABILIZER UP
VALVE – OPEN
CIRCUIT

2

33231 Voltage on UGM pin J2-19

indicates solenoid
disconnected.

N

Check for continuity through this circuit.

Inspect wiring for physical damage.

Note: An open circuit voltage of nearly
8.0V exists on this UGM pin for circuit
diagnostic purposes.

RIGHT
STABILIZER UP
VALVE – SHORT
TO BATTERY

33232 Voltage on UGM pin J2-8

indicates STB fault.

N

Check for continuity through this circuit.

Inspect wiring for physical damage.

Note: The wire on the low side of the coil
provides current feedback to J3-14 and
can open circuit the electrical path to
ground to prevent current flow through the
coil (to prevent function movement).

RIGHT
STABILIZER UP
VALVE – SHORT
TO GROUND

33233 Loss of current feedback on

UGM pin J3-6 while driving
coil via UGM pin J2-8.

N

Check for continuity through this circuit.

Inspect wiring for physical damage.

RIGHT
STABILIZER –
CURRENT
FEEDBACK
READING TOO
LOW

33335 Current feedback on

UGM pin J3-6 > 250ma; but
difference from commanded
current while driving coil via
UGM pin J2-8 > 125ma for 1
second.

N

Check for continuity through this circuit.

Inspect wiring for physical damage.

Check the current on the Feedback wire
returning to UGM pin J3-14. This current
should read within 20ma of the value
commanded as read on the Analyzer
under Diagnostics/Ground for either Left
Stabilizer Up or Down functions;
otherwise, there is a degraded
connection. If the value does not track,
temporarily swap connections to assess
whether and how the fault follows the
wiring.

Note: The wire on the low side of the coil
provides current feedback to J3-14 and
will measure an open circuit when a STB
condition exists because the UGM has
open circuited the electrical path to
ground to prevent current flow through the
coil (to prevent function movement).

Help Message

1

DTC

Fault Condition

(for configurable items,

fault applies only if

configured)

Fault

Requires

AccuPlace

Reset?

Action(s)