G10-55A & G12-55A AccuPlace

Electrical System

FRAME LEVEL
LEFT VALVE –
OPEN CIRCUIT

33234 Voltage on UGM pin J2-11

indicates solenoid
disconnected.

N

Check for continuity through this circuit.

Inspect wiring for physical damage.

Note: An open circuit voltage of nearly
8.0V exists on this UGM pin for circuit
diagnostic purposes.

FRAME LEVEL
LEFT VALVE –
SHORT TO
BATTERY

33235 Voltage on UGM pin J2-11

indicates STB fault.

N

Check for continuity through this circuit.

Inspect wiring for physical damage.

FRAME LEVEL
LEFT VALVE –
SHORT TO
GROUND

33236 Loss of current feedback on

UGM pin J3-2 while driving
coil via UGM pin J2-11.

N

Check for continuity through this circuit.

Inspect wiring for physical damage.

FRAME LEVEL
RIGHT VALVE -
OPEN CIRCUIT

33237 Voltage on UGM pin J2-22

indicates solenoid
disconnected.

N

Check for continuity through this circuit.

Inspect wiring for physical damage.

Note: An open circuit voltage of nearly
8.0V exists on this UGM pin for circuit
diagnostic purposes.

FRAME LEVEL
RIGHT VALVE –
SHORT TO
BATTERY

33238 Voltage on UGM pin J2-22

indicates STB fault.

N

Check for continuity through this circuit.

Inspect wiring for physical damage.

Note: The wire on the low side of the coil
provides current feedback to J3-14 and
can open circuit the electrical path to
ground to prevent current flow through the
coil (to prevent function movement).

FRAME LEVEL
RIGHT VALVE –
SHORT TO
GROUND

33239 Loss of current feedback on

UGM pin J3-2 while driving
coil via UGM pin J2-22.

N

Check for continuity through this circuit.

Inspect wiring for physical damage.

FRAME LEVEL –
CURRENT
FEEDBACK
READING TOO
LOW

33336 Current feedback on UGM

pin J3-2 > 250ma; but
difference from commanded
current while driving coil via
UGM pin J2-22 > 125ma for
1 second.

N

Check for continuity through this circuit.

Inspect wiring for physical damage.

Check the current on the Feedback wire
returning to UGM pin J3-14. This current
should read within 20ma of the value
commanded as read on the Analyzer
under Diagnostics/Ground for either Left
Stabilizer Up or Down functions;
otherwise, there is a degraded
connection. If the value does not track,
temporarily swap connections to assess
whether and how the fault follows the
wiring.

Help Message

1

DTC

Fault Condition

(for configurable items,

fault applies only if

configured)

Fault

Requires

AccuPlace

Reset?

Action(s)