Electrical System

9.98

G10-55A & G12-55A AccuPlace

CANBUS
FAILURE –
TELESCOPE
VALVE

6627

ISP communicates
SPN/FMI: 2162/11

Y

Cycle power to see if fault clears.

If multiple CAN Bus faults are occurring,
the integrity of connections and continuity
of the entire CAN Bus must be checked.
Otherwise, with power off, unplug the Tele
Valve and with a multimeter verify
approximately 60ohms between CANH
and CANL in the machine harness. Turn
power on a verify +12V between power
and ground pins. Also, verify that the
ground pin has less than 1.0ohms
resistance to a good chassis (B-)
connection. Turn power off, reconnect
Tele Valve, and power on. If fault still
exists, unplug connector to Tele Valve and
verify the connectivity in the 12-pin
Deutsch connector. Remove the wedge
and pull each termination back past the
rubber seal. Lightly tug on each wire and
inspect the crimp.

Check the integrity of the M12 connector
termination at the green CAN Distribution
module. Disconnect, clean, and
reconnect. Do not add dielectric grease,
as the pins may not engage properly. The
spare connection on the CAN Distribution
module may also be used as a means to
verify integrity of the M12 connection. The
functionality of the system will remain
unchanged if the spare M12 connection is
used.

Note: Although similar, the Lift Valve and
Tele Valve harnesses are not directly
interchangeable for troubleshooting
purposes because the current feedback
wires populate different connector pins.