Electrical System

9.90

G10-55A & G12-55A AccuPlace

ISP – PRESSURE
TOO HIGH

4585

ISP controller detects too
high pressure from Pressure
Sensor 1 or 2.

N

Cycle power to clear DTC; if DTC still
present, remove controller and clean
around pressure transducers. Ensure
transducer gaskets are in place and
reinstall/torque in sequence (Refer to
Section 8.8.11, “Valve Controllers.”). If
fault is still present, controller replacement
is required.

CAUTION: HIGH OIL PRESSURE
WITHIN VALVE AND CONTROLLER.

LIFT VALVE –
TEMPERATURE
SENSOR
VOLTAGE OUT
OF RANGE

4586

Lift valve controller detects
too low or high voltage from
Temperature Sensor 1 or 2.

N

Cycle power to clear DTC; if DTC still
present, controller replacement required.
Ensure transducer gaskets are in place
and reinstall/torque in sequence (Refer to
Section 8.8.11, “Valve Controllers.”).

CAUTION: HIGH OIL PRESSURE
WITHIN VALVE AND CONTROLLER.

Removing controller may cause cylinder
leakage. Brace/block boom before
removing controller.

TELESCOPE
VALVE –
TEMPERATURE
SENSOR
VOLTAGE OUT
OF RANGE

4587

Tele valve controller detects
too low or high voltage from
Temperature Sensor 1 or 2.

N

Cycle power to clear DTC; if DTC still
present, controller replacement required.
Ensure transducer gaskets are in place
and reinstall/torque in sequence (Refer to
Section 8.8.11, “Valve Controllers.”).

CAUTION: HIGH OIL PRESSURE
WITHIN VALVE AND CONTROLLER.

Removing controller may cause cylinder
leakage. Brace/block boom before
removing controller.

FORK VALVE –
TEMPERATURE
SENSOR
VOLTAGE OUT
OF RANGE

4588

Fork valve controller detects
too low or high voltage from
Temperature Sensor 1 or 2.

N

Cycle power to clear DTC; if DTC still
present, controller replacement required.
Ensure transducer gaskets are in place
and reinstall/torque in sequence (Refer to
Section 8.8.11, “Valve Controllers.”).

CAUTION: HIGH OIL PRESSURE
WITHIN VALVE AND CONTROLLER.

ISP –
TEMPERATURE
SENSOR
VOLTAGE OUT
OF RANGE

4589

ISP controller detects too
low or high voltage from
Temperature Sensor 1 or 2.

N

Cycle power to clear DTC; if DTC still
present, controller replacement required.
Ensure transducer gaskets are in place
and reinstall/torque in sequence (Refer to
Section 8.8.11, “Valve Controllers.”).

CAUTION: HIGH OIL PRESSURE
WITHIN VALVE AND CONTROLLER.

Help Message

1

DTC

Fault Condition

(for configurable items,

fault applies only if

configured)

Fault

Requires

AccuPlace

Reset?

Action(s)