9.107

G10-55A & G12-55A AccuPlace

Electrical System

CHASSIS TILT
SENSOR NOT
GAIN
CALIBRATED

9915

Gain calibrations not
properly set at factory.

Y

Cycle power to see if fault clears.

Calibrate tilt sensor. Refer to Section
9.15.5, “Calibrations.”
If tilt sensor will not
calibrate, record all Machine Setup and
Personality parameters. Next, toggle
model from existing model to another
machine model and back. This will
effectively set EEPROM values to default.
Adjust the Machine Setup and Personality
parameters to previous values. If fault
persists, UGM replacment is required.

If Chassis Tilt sensor will not calibrate or
fault still exists after calibration and
resetting of EEPROM, UGM replacement
is required.

CHASSIS TILT
SENSOR GAIN
OUT OF RANGE

9916

Gain calibration at factory
outside acceptable range.

Y

Cycle power to see if fault clears.

Calibrate tilt sensor. Refer to Section
9.15.5, “Calibrations.”
If tilt sensor will not
calibrate, record all Machine Setup and
Personality parameters. Next, toggle
model from existing model to another
machine model and back. This will
effectively set EEPROM values to default.
Adjust the Machine Setup and Personality
parameters to previous values. If fault
persists, UGM replacment is required.

If Chassis Tilt sensor will not calibrate or
fault still exists after calibration and
resetting of EEPROM, UGM replacement
is required.

FUNCTIONS
LOCKED OUT –
LIFT VALVE
SOFTWARE
VERSION
IMPROPER

2

9981

Lift valve controller has
incompatible software
version.

N

Software update required.

FUNCTIONS
LOCKED OUT –
TELESCOPE
VALVE
SOFTWARE
VERSION
IMPROPER

2

9982

Telescope valve controller
has incompatible software
version.

N

Software update required.

Help Message

1

DTC

Fault Condition

(for configurable items,

fault applies only if

configured)

Fault

Requires

AccuPlace

Reset?

Action(s)