JLG G12-55A AccuPlace Service Manual User Manual

Page 227

Advertising
background image

9.109

G10-55A & G12-55A AccuPlace

Electrical System

INCOVA
CALIBRATION
DATA NOT
WRITTEN

9988

The UGM to ISP Calibration
data was not successfully
written to ISP.

Y

This fault may occur when the CAN Bus
communications are of poor quality.

Cycle power to see if fault clears.

Check the amount of CAN1 traffic and
errors via the Analyzer under
DIAGNOSTICS/CAN STATISTICS.
Expected ranges of values are CAN1 Rx/
s ~ 600-700; CAN1 Tx/s ~ 100-150; CAN1
ERR F/S = 0. Troubleshoot CAN Bus if
errors are present or transmit/receive
values are suspect.

INCOVA
PERSONALITIES
NOT WRITTEN

9989

The UGM to ISP
Personalities data was not
successfully written to ISP.

Y

This fault may occur when the CAN Bus
communications are of poor quality.

Cycle power to see if fault clears.

Check the amount of CAN1 traffic and
errors via the Analyzer under
DIAGNOSTICS/CAN STATISTICS.
Expected ranges of values are CAN1 Rx/
s ~ 600-700; CAN1 Tx/s ~ 100-150; CAN1
ERR F/S = 0. Troubleshoot CAN Bus if
errors are present or transmit/receive
values are suspect.

Help Message

1

DTC

Fault Condition

(for configurable items,

fault applies only if

configured)

Fault

Requires

AccuPlace

Reset?

Action(s)

Advertising
This manual is related to the following products: