6.1.5 Jog

In a jogging motion, the motor receives a command to move at a fixed speed. The AC and
DC parameters indicate the acceleration or deceleration to the desire speed.

Jog motions may be initiated any time by using the JV command, and not necessarily
from a stationary state. The jog mode decisions, made every position control cycle, are
given in the following flowchart.

Start

JV > 0 and

Speed > JV?

Yes

Apply DC

Speed = JV?

Yes

Apply AC

Maintain JV

JV< 0 and

Speed < JV?

Yes

Apply DC

Figure 6-5: Jog Decisions Flowchart

All parameters in the flowchart — including AC, DC, JV and the position target — are
updated by a BG command or by its hardware equivalent (refer to the IL[N] command in
the

SimplIQ for Steppers

Command Reference Manual).

Jog motions can continue indefinitely. The position reference jumps by XM[2] - XM[1]
when it reaches the modulo boundary, but the speed remains constant. The jog motion
parameters are summarized in the following table:

Parameter Action

AC

Acceleration, in counts/second

2

DC

Deceleration, in counts/second

2

SF

Smooth factor, in milliseconds

JV Jog

velocity

Table 6-6: Jog Motion Parameters

The JV command specifies that the next motion will be a jog, and also what speed the jog
will target.

SimplIQ for Steppers Application Note

The Position Reference Generator

MAN-STECR (Ver. 1.1)

45