Object 0x2090: firmware download, Object 0x208a: begin time -13, Object 0x2090: firmware download -13 – ElmoMC CANopen DS 301 Implementation Guide User Manual

Page 90: 0x208a, 0x2090, Simpliq

Advertising
background image

Note: Network states 1 & 4 (disconnect & stop, respectively) can not be retrieved

using the CAN controller status object, since neither the PDO nor the SDO is
communicated. However, the DD command (RS-232 serial communication) can be
used in these cases. The node state can also be retrieved using the Heartbeat
Producer mechanism.

Object 0x208A: Begin time
This object receives an absolute time for a simultaneous Motion Begin (BG). The time
resolution for this object is 1 microsecond. For more information, refer to the BT
command section in the

SimplIQ

Command Reference Manual and to

Chapter 8

of this

manual.

ƒ

Object description:

Index 208Ah

Name Begin

time

Object code

VAR

Data type

UNSIGNED32

Category Optional

ƒ

Entry description:

Access Read/Write

PDO mapping

No

Value range

No

Default value

No

Object 0x2090: Firmware download
This object is used to download controller firmware using S-record format.

ƒ

Object description:

Index 2090h

Name Download

firmware

Object code

DOMAIN

Data type

Visible String

Category Optional

ƒ

Entry description:

Access Write

only

PDO mapping

No

Value range

No

CANopen DS 301 Implementation Guide

Manufacturer-specific Objects

MAN-CAN301IG (Ver. 2.1)

13-13