Configuration Ownership—Reset Ownership

The connection between the owner and the Guard I/O module is based on the
following:

Guard I/O DeviceNet node address
Guard I/O safety network number
GuardLogix slot number
GuardLogix safety network number
Path from GuardLogix controller to Guard I/O module
Configuration signature

If any of these change, the connection between the controller and the Guard I/O
module is lost. Reset the Guard I/O module to attempt to reestablish the
connection by using this procedure.

The most common use of resetting the device is when the 1791DS module has
previously had a safety connection to another controller. Until that prior owner is
reset, the module will not make a new safety connection.

1. When online with the 1791DS module, right-click the module and choose

Reset Safety Device.