Table 39 - Safety Input Parameters

Parameter Name

Value

Description

Input Point Operation Type

Single Channel

Use as single channel.

Dual-channel Equivalent

Use as dual-channel. Normal when both channels are ON or OFF.

Dual-channel Complementary

Use as dual-channel. Normal when one channel is ON and the other channel is OFF.

Input Point Mode

Not Used

External input device is not connected.

Safety Test Pulse

Use with a contact output device and in combination with a test output. By using this setting, short-circuits
between input signal lines and the power supply (positive side) and short-circuits between input signal
lines can be detected.

Safety

A solid-state output safety sensor is connected.

Standard

A standard device, such as a reset switch, is connected.

Safety Input Test Source

Not Used

The test output that is used with the input.

Test Output 0

Test Output 1

Test Output 2

Test Output 3

Input Delay Time Off -> On

0…126 ms (in increments of
6 ms)

Filter time for OFF to ON transition.

Input Delay Time On -> Off

0…126 ms (in increments of
6 ms)

Filter time for ON to OFF transition.

IMPORTANT

If the test pulse from test output is set to the Safety Input Channel mode,
the safety-input test source and pulse test output of the test output must
be set to the Test Output mode.