Connect communication connectors, Set the node address – Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual

Page 46

Advertising
background image

46

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Chapter 3

Install and Connect Your Modules

Connect Communication
Connectors

Colored stickers on the communication connector match the colors of the wires
to be inserted. Check that the colors of the wires match when wiring the
connectors. The colors are as follows.

The internal power for the module is supplied from the communication power
supply (V+, V-).

Set the Node Address

To set the node address, follow this procedure.

Figure 23 - Sample Node Address Digits

1. Set the node address by using the two rotary switches on the front panel of

the module, noting that the default setting is 63 and a value between
00…63 is valid for proper use.

2. Use the left rotary switch to set the tens digit of node address (decimal).

3. Use the right rotary switch to set the ones digit.

If the node address switches are set from 64…99, the node address needs to be set
from RSNetWorx for DeviceNet software.

Color

Signal

Red

Power cable positive side (V+)

White

High side of communication data (CAN_H)

-

Shield

Blue

Low side of communication data (CAN_L)

Black

Power cable negative side (V-)

IMPORTANT

When connecting a communication connector with the module,
tighten the screws on the communication connector to the specified
torque setting as shown in the installation instructions.

IMPORTANT

The node-address setting rotary switches must be set while the
communication power supply is turned off.

Tens Digit

Ones Digit

|

|

|

|

|

2

4

6

8

0

|

|

|

|

|

2

4

6

8

0

X1

X10