Chapter 8

Interpret Status Indicators

Table 12 - Configuration Lock (LOCK) Indicator

State

Status

Description

Recommended Action

Off

No configuration

Invalid configuration data.

Provide valid configuration data.

The configuration is owned by
a CIP safety originator, such as
GuardLogix software

The configuration is owned by a CIP safety originator, such as
GuardLogix software.

None.

Solid yellow

Locked

Valid configuration, locked by a network configuration tool such
as RSNetWorx for DeviceNet software.

None.

Flashing yellow

Not locked

Valid configuration, owned by a software configuration tool
such as RSNetWorx for DeviceNet software.

None.

Table 13 - 24V DC Input Power Indicator

State

Status

Description

Recommended Action

Off

No power

No power is applied.

Apply power to this section.

Solid green

Normal operation

The applied voltage is within specifications.

None.

Solid yellow

Input power out of
specification

The input power is out of specification.

Check your connectors, wiring, and voltages, For additional
information, see the applicable installation instructions.

Table 14 - 24V DC Output Power Indicator

State

Status

Description

Recommended Action

Off

No power

No power is applied.

Apply power to this section.

Solid green

Normal operation

The applied voltage is within specifications.

None.

Solid yellow

Output power out of
specification

The output power is out of specification.

Check your connectors, wiring, and voltages. For additional
information, see the applicable installation instructions.

Table 15 - Safety Input Indicator

State

Status

Description

Recommended Action

Off

Safety input off or module
being configured

The safety input is off or the module is being configured.

Turn the safety input on or wait for the module to be configured.

Solid yellow

Safety input on

The safety input is on.

None.

Solid red

Fault detected

A fault in the external wiring or input circuit detected.

Check configuration, field wiring, and devices. If no anomaly is
found, replace the module.

Flashing red

Partner fault detected

A fault in the partner input circuit of a dual input configuration
detected.

Check the field wiring and verify your configuration for the
partner circuit. If no anomaly is found, replace the module.