Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Chapter 2

Understand the Operation of Safety Functions

Safety Outputs

Read this section for information about safety outputs.

Safety Output with Test Pulse

When the safety output is on, the safety output can be test pulsed, as shown in
the figure and table.

Using this function, short-circuits between output signal lines and the power
supply (positive side) and short-circuits between output signal lines can be
detected. If an error is detected, the safety output data and individual safety
output status turn off.

Figure 19 - Test Pulse in a Cycle

Cat. No.

Pulse Width (X)

Pulse Period (Y)

1732DS-IB8

Not applicable

Not applicable

1732DS-IB8XOBV4

700 μs

600 ms

1791DS-IB12

Not applicable

Not applicable

1791DS-IB8XOB8

470 μs

648 ms

1791DS-IB4XOW4

Not applicable

Not applicable

1791DS-IB8XOBV4

700 μs

600 ms

1791DS-IB16

Not applicable

Not applicable

IMPORTANT

To prevent the test pulse from causing the connected device to
malfunction, pay careful attention to the input response time of the device.