Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual

Page 149

Advertising
background image

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

149

Get Point Status from Modules by Using Explicit Messaging

Appendix A

These tables provide reference data concerning input and output data.

Table 18 - Input Data for 1791DS-IB12, 1791DS-IB8XOB8, 1791DS-IB4XOW4 Modules

Instance
Hex
(decimal)

Module

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

203
(515)

1791DS-IB4XOW4

0

Reserved

Safety Input 3 Safety Input 2 Safety Input

1

Safety Input
0

204
(516)

1791DS-IB8XOB8

0

Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input

1

Safety Input
0

20C
(524)

1791DS-IB12

0

Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input

1

Safety Input
0

1

Reserved

Safety Input
11

Safety Input
10

Safety Input
9

Safety Input
8

224
(548)

1791DS-IB12

0

Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input

1

Safety Input
0

1

Safety Input 7
Status

Safety Input 6
Status

Safety Input 5
Status

Safety Input 4
Status

Safety Input 3
Status

Safety Input 2
Status

Safety Input
1 Status

Safety Input
0 Status

22C
(556)

1791DS-IB12

0

Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input

1

Safety Input
0

1

Safety Input 3
Status

Safety Input 2
Status

Safety Input 1
Status

Safety Input 0
Status

Safety Input
11

Safety Input
10

Safety Input
9

Safety Input
8

2

Safety Input
11 Status

Safety Input
10 Status

Safety Input 9
Status

Safety Input 8
Status

Safety Input 7
Status

Safety Input 7
Status

Safety Input
5 Status

Safety Input
4 Status

300
(768)

1791DS-IB12,
1791DS-IB8XOB8,
1791DS-IB4XOW4

0

Reserved

Output
Power Error

Input Power
Error

310
(784)

1791DS-IB12

0

Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input

1

Safety Input
0

1

Muting Lamp
Status

Combined
Safety In
Status

Reserved

Safety Input
11

Safety Input
10

Safety Input
9

Safety Input
8

311
(785)

1791DS-IB12

0

Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input

1

Safety Input
0

1

Safety Input 3
Status

Safety Input 2
Status

Safety Input 1
Status

Safety Input 0
Status

Safety Input
11

Safety Input
10

Safety Input
9

Safety Input
8

2

Safety Input
11 Status

Safety Input
10 Status

Safety Input 9
Status

Safety Input 8
Status

Safety Input 7
Status

Safety Input 6
Status

Safety Input
5 Status

Safety Input
4 Status

3

Muting Lamp
Status

Reserved

312
(786)

1791DS-IB12

0

Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input

1

Safety Input
0

1

Safety Input 3
Status

Safety Input 2
Status

Safety Input 1
Status

Safety Input 0
Status

Safety Input
11

Safety Input
10

Safety Input
9

Safety Input
8

2

Safety Input
11 Status

Safety Input
10 Status

Safety Input 9
Status

Safety Input 8
Status

Safety Input 7
Status

Safety Input 6
Status

Safety Input
5 Status

Safety Input
4 Status

3

Muting Lamp
Status

Reserved

Test Output 3
Status

Test Output 2
Status

Test Output 1
Status

Test Output 0
Status

320
(800)

1791DS-IB8XOB8

0

Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input

1

Safety Input
0

1

Muting Lamp
Status

Combined
Safety In
Status

Combined
Safety Out
Status

Reserved