Using a test output with a safety input – Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual

Page 27

Advertising
background image

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

27

Understand the Operation of Safety Functions

Chapter 2

Using a Test Output with a Safety Input

A test output can be used in combination with a safety input for short circuit
detection. Configure the test output as a pulse test source and associate it to a
specific safety input.

The test output can also be configured for a power supply to source 24V DC for
an external device, for example, a light curtain.

Figure 11 - Example Use of a 1791DS-IB12 Module

Figure 12 - Test Pulse in a Cycle

Cat. No.

Pulse Width (X)

Pulse Period (Y)

1732DS-IB8

500 μs

600 ms

1732DS-IB8XOBV4

500 μs

600 ms

1791DS-IB12

700 μs

648 ms

1791DS-IB8XOB8

700 μs

648 ms

1791DS-IB4XOW4

700 μs

648 ms

1791DS-IB8XOBV4

500 μs

600 ms

1791DS-IB16

500 μs

600 ms

24V DC Output with Test Pulse

External Contact

Safety Input
Terminal

24V

44078

X

OUT

Y

On

Off