Configure Modules with the Logix Designer Application

Values and States of Tags

Use this table to determine the values and states of the tags.

Data

Description

Input data Safety Input Data

SAFETY

Indicates the ON/OFF status of each input circuit.

·ON: 1 OFF: 0

Combined Safety Input Status
SAFETY

An AND of the status of all input circuits.

·All circuits are normal: 1
·An error was detected in one or more input circuits: 0

Individual Safety Input Status
SAFETY

Indicates the status of each input circuit.

· Normal: 1 Fault (Alarm): 0

Combined Safety Output Status
SAFETY

An AND of the status of all safety output circuits.

·All circuits are normal: 1
·An error has been detected in one or more output circuits: 0

Individual Safety Output Status
SAFETY

Indicates the status of each safety output circuit.

·Normal: 1 Fault (Alarm): 0

Muting Lamp Status
SAFETY

Indicates the status when circuit T3, T7, T11, and T15 is configured
as the muting lamp output.

·Normal: 1 Fault (Alarm): 0

Output Readback
STANDARD

Monitors the presence of 24V on the output circuit. Readback is ON
(1) if 24V is on output terminal.

·ON: 1 OFF: 0

Individual Test Output Status
STANDARD

Indicates the status of each of the test output circuits.

·Normal:1 Fault (Alarm): 0

Output
data

Safety Output Data
SAFETY

Controls the safety output.

·ON: 1 OFF: 0

Standard Output Data
STANDARD

Controls the test output when Test Output mode is set to a standard
output.

·ON: 1 OFF: 0

IMPORTANT

Safety denotes information the controller can use in safety-related
functions. Standard denotes additional information that must not be relied
on for safety functions.