Configuration Reference Information

Understanding
Parameter Groups

The modules have these parameter groups:

General Parameters

Safety Input Parameters

Test Output Parameters

Safety Output Parameters

Set all parameters by using the Logix Designer application or RSNetWorx for
DeviceNet software.

Topic

Page

Understanding Parameter Groups

165

Allocate Remote I/O

167

I/O Data Supported by Each Module

167

Table 38 - General Parameters

Parameter Name

Value

Description

Default

Safety Output Error Latch Time

0…65,530 ms (in increments of
10 ms)

Safety output errors are latched for this time.

1000 ms

Safety Input Error Latch Time

0…65,530 ms
(in increments of 10 ms)

Safety input or test output errors are latched for this time.

1000 ms

Test Output Idle State

Clear OFF or Keep Output Data

Definition of output data is in idle state.

Clear OFF