Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual

Page 122

Advertising
background image

122

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Chapter 7

Considerations When Replacing Guard I/O Modules

If the project is configured as ‘Configure Only When No Safety Signature Exists’,
follow the appropriate steps to replace a Guard I/O module based on your
scenario.

Scenario 1 - New Module is Out-of-box and Safety Signature Exists

1. Remove the old I/O module and install the new module.

2. Right-click your GuardLogix controller and choose Properties.

3. Click

to the right of the safety network number to open the Safety

Network Number dialog box.

4. Click Set.

GuardLogix Project
Safety Signature
Exists

Replacement Module
SNN

Fault

Action Required

Yes

Out-of-box

SNN not set, device
out-of-box

Click Set.

Refer to Scenario 1 - New Module is
Out-of-box and Safety Signature
Exists on page 122

.

No

Out-of-box

None

None.

Yes or No

Same as original

None

None.

Yes

Different from original

SNN mismatch
SNN not set, device
out-of-box

1. Click Reset Ownership.
2. Click Set.

Refer to Scenario 2 - New Module
SNN is Different from Original and
Safety Signature Exists on page 123.

No

Different from original

SNN mismatch

Click Reset Ownership.

Refer to Scenario 3 - New Module
SNN is Different from Original and
No Safety Signature Exists on
page 124

.