Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Chapter 6

Configure Modules in RSNetWorx for DeviceNet Software

Configure the Output Channel

Follow these steps to configure the safety output channel.

1. Double-click Output Points xx/xx.

The Output Points folder expands. In this example, 00/01 is shown.

2. Assign the Operation Type.

3. Assign the channel Mode.

Configure Input and Output Error Latch Times

Follow these steps to configure the input and output error latch times.

1. Double-click General.

Choose

Description

Single

(1)

The output is treated as a single channel.

Dual (default)

The Guard I/O module treats the outputs as a pair. It always sets them
HI or LO as a matched pair. Safety logic must set both of these outputs
ON or OFF as the same time or the module declares a channel fault.

(1) Does not apply to bipolar outputs.

Choose

Description

Not Used (default)

The output is disabled.

Safety

The output point is enabled, and it does not perform a pulse test on
the output.

Safety Pulse Test

The output point is enabled and performs a pulse test on the output.
When the output is energized, the output pulses LO briefly. The pulse
test detects if 24V remains on the output terminal during this LO
pulse due to a short to 24V or if the output is shorted to another
output terminal.