Understand the Operation of Safety Functions

Chapter 2

Safety Input Fault Recovery

If an error is detected, the safety input data remains in the off state. Follow this
procedure to activate the safety input data again.

1. Remove the cause of the error.

2. Place the safety input (or safety inputs) into the safe state.

The safety input status turns on (fault cleared) after the input-error latch
time has elapsed and the I/O indicator (red) turns off. The input data can
now be controlled.

Input Delays

On-delay - An input signal is treated as Logic 0 during the on-delay time (0…126
ms, in increments of 6 ms) after the input contact’s rising edge. The input turns
on only if the input contact remains on after the on-delay time has elapsed. This
helps prevent rapid changes of the input data due to contact bounce.

Figure 17 - On-delay

Off-delay - An input signal is treated as Logic 1 during the off-delay time (0…126
ms, in increments of 6 ms) after the input contact’s falling edge. The input turns
off only if the input contact remains off after the off delay time has elapsed. This
helps prevent rapid changes of the input data due to contact bounce.

Figure 18 - Off-delay

ON

OFF

ON

OFF

Remote I/O

Data Safety

Input

Input Signal

ON-delay

44094

On-delay

Input Signal

ON
OFF

ON
OFF

Remote I/O Data
Safety Input

OFF

ON

OFF

Safety Input

Input Signal

OFF-delay

44095

Remote I/O Data
Safety Input

Input Signal

ON
OFF

ON
OFF

Off-delay