Allocate remote i/o, I/o data supported by each module, Test output parameters – Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual

Page 167: Safety output parameters

Advertising
background image

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

167

Configuration Reference Information

Appendix C

Allocate Remote I/O

The module internally stores I/O allocation data. Use the Logix Designer
application or RSNetWorx for DeviceNet software to set the connection paths
for the allocation of I/O data in the master unit. No settings are made by default.
Be sure to set the required connection paths.

The module stores this I/O data:

SAFETY: Information the controller can use in safety-related functions
STANDARD: Additional information that must not be relied on for

safety functions

I/O Data Supported by
Each Module

These tables show the I/O data supported by each module. Refer to I/O
Assembly Data for data arrangements.

You can allocate up to four items of I/O-data safety connections, including one
output, and up to two items of I/O-data standard connections for the master unit
(such as a scanner).

Table 40 - Test Output Parameters

Parameter Name

Value

Description

Default

Test Output Mode

Not Used

An external device is not connected.

Not Used

Standard

The output is connected to a standard device.

Pulse Test

A contact output device is connected. Use in combination with a safety
input.

Power Supply

The power supply of a Safety Sensor is connected. The voltage supplied to I/
O power (V, G) is output from the test output terminal.

Muting Lamp Output (Terminal T3
or T7 only)

An indicator is connected and turned ON to detect broken lines in an
external indicator.

Test Output Fault Action

(1)

Clear OFF

Action to perform when a communication error is detected.

Clear OFF

Hold Last Data

(1) Not directly related to safety.

Table 41 - Safety Output Parameters

Parameter Name

Value

Description

Default

Output Point Mode

Not Used

An external output devices is not connected.

Not Used

Safety

When the output is ON, the test pulse is not output (remains ON).

Safety Pulse Test

By using this function, short-circuits between output signal lines and the power supply
(positive side) and short-circuits between output signal lines can be detected.

Output Point Operation Type

Single Channel

Use as single channel.

Dual-channel

Dual-channel

Use as dual-channel. When both channels are normal, outputs can be turned ON.