Configure Modules in RSNetWorx for DeviceNet Software

If you see the following message after attempting to download, the likely scenario
is that the 1791DS module was previously owned by a different safety controller.
You must reset the owner before the 1791DS module will make a new safety
connection.

To reset the 1791DS module, right-click the module and choose Reset Safety
Device.

The Reset Safety Device dialog box appears.

Check Password and Safety Network Number so that the 1791DS module is
totally reset. Click Reset.