Interpret Status Indicators

Chapter 8

1791DS-IB12,
1791DS-IB8XOB8, and
1791DS-IB4XOW4
Status Indicators

Refer to the tables for information on how to interpret status indicators on the
1791DS-IB12, 1791DS-IB8XOB8, and 1791DS-IB4XOW4 modules.

Table 3 - Module Status (MS) Indicator

State

Status

Description

Recommended Action

Solid green

Normal

Normal operating status.

None- normal operation.

Flashing green

Standby

Waiting for safety communication from the safety controller.

Wait for module to establish communication.

Solid red

Fatal fault

Hardware fault.

Check for electrical noise and eliminate the source. If the
anomaly persists, replace the module.

Flashing red

Minor fault

Switch settings incorrect.

Correct the switch settings.

Flashing green/
red

Initialization status

The module is performing initialization process or waiting for
configuration.

Wait for the configuration to complete.

Off

No power

Power is not being supplied to the module.

Supply power to the module.

Waiting for initial processing to start.

Wait for processing to start.

The module is being reset.

Wait for the module to reset.

Table 4 - Network Status (NS) Indicator

State

Status Description

Recommended

Action

Solid green

Online/connected

Network is operating normally (communication established).

None - normal operation.

Flashing green

Online/not connected

Network is operating normally, however, communication is not
established.

Verify your network and module configuration.

Solid red

Fatal link failure

Communication fault.

Correct the communication fault.

Module detected that network communication is not possible.

Node address duplication detected.

Abusive fault detected.

Flashing red

Minor communication fault

Communication timeout.

Correct the communication fault.

Off

Not online or not powered

Waiting for node address duplication check at the master.

Wait for check to complete.

The power supply is off.

Apply power.

Table 5 - Configuration Lock (LOCK) Indicator

State

Status

Description

Recommended Action

Solid yellow

Normal and locked

Normal configuration, and configuration is locked by RSNetWorx
for DeviceNet software.

None.

Flashing yellow

Normal and not locked

Normal configuration, but configuration is not locked in the
module.

None.

Off

Configuration not performed

Configuration has not been performed.

Perform the configuration.