Considerations When Replacing Guard I/O Modules

Chapter 7

The Set Safety Network Number in Module confirmation dialog box
appears.

5. Verify that the Network Status (NS) status indicator is alternating red/

green on the correct module before clicking Yes to set the SNN and accept
the replacement module.

6. Follow your company-prescribed procedures to functionally test the

replaced I/O module and system and to authorize the system for use.

Scenario 2 - New Module SNN is Different from Original and Safety Signature Exists

1. Remove the old I/O module and install the new module.

2. Right-click your Guard I/O module and choose Properties.

3. Click the Safety tab.

4. Click Reset Ownership.

5. Click OK.

6. Right-click your GuardLogix controller and choose Properties.