Two-hand monitor – Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual

Page 49

Advertising
background image

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

49

Wiring Examples

Chapter 4

Two-hand Monitor

This example shows wiring and controller configuration when using a Guard I/O
module with a two-hand monitor. If used in combination with the programs in a
safety controller, this wiring is Safety Category 4 in accordance with EN 954-1
wiring requirements.

Controller
Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Dual-channel Complementary

Dual-channel Safety Input 0/1 Discrepancy Time

100 ms (application dependent)

Safety Input 1

Safety Input 1 Channel Mode

Test Pulse from Test Output

Safety Input 1 Test Source

Test Output 1

Safety Input 2

Safety Input 2 Channel Mode

Test Pulse from Test Output

Safety Input 2 Test Source

Test Output 0

Dual-channel Safety Input 2/3 Mode

Dual-channel Complementary

Dual-channel Safety Input 2/3 Discrepancy Time

100 ms (application dependent)

Safety Input 3

Safety Input 3 Channel Mode

Test Pulse from Test Output

Safety Input 3 Test Source

Test Output 1

Test Output 0

Test Output 0 Mode

Pulse Test Output

Test Output 1

Test Output 1 Mode

Pulse Test Output

I0

I2

I1

I3

IN+

IN-

T0

T1

E1

T1

T2

T1

T3

S11

31803-M

S12

-

+

FE

E1: 24V DC Power Supply
S11 and S12: Two-hand
Switches

Advertising
This manual is related to the following products: