Bipolar output examples, Dual-load bipolar outputs – Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual

Page 55

Advertising
background image

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

55

Wiring Examples

Chapter 4

Bipolar Output Examples

Read this section for bipolar output examples by application. For details, refer to
the installation instructions for each catalog number.

Dual-load Bipolar Outputs

This example shows wiring and controller configuration when using a Guard I/O
module with solid-state outputs in Dual-channel mode.

Note that all safety outputs of this Guard I/O module are permanently
configured for use as Dual-channel mode only. When used in combination with
the programs of the safety controller, this circuit configuration is Safety Category
4 in accordance with EN 954-1 requirements.

IN+

IN-

OUT+

OU T-

FE

O0

P

M

P

M

O1

L-

L-

S+

S+

02

03

FE

I0

K1

K2

I1

T0

T2

T1

T3M

I2

31807-M

I3

M

K1

K2

K2

PS2

PS1

K1

PS1, PS2: User 24V DC power supply. (A single
power supply can be used for both input and
output power.)

Controller
Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Pulse Test Output

Safety Output 0

Safety Output 0 Channel Mode

Safety Pulse Test

Safety Output 1

Safety Output 1 Channel Mode

Safety Pulse Test