Chapter 2

Understand the Operation of Safety Functions

Controlling Devices

See this table for information about controlling devices.

Safety Precautions

ATTENTION: Use appropriate devices as indicated in the Controlling
Device Requirements
table. Serious injury may occur due to loss of
safety functions.

Table 2 - Controlling Device Requirements

Device

Requirement

Allen-Bradley Bulletin Safety Components

Emergency stop switches

Use approved devices with direct opening mechanisms complying with IEC/EN
60947-5-1.

Bulletin 800F, 800T

Door interlocking switches,
limit switches

Use approved devices with direct opening mechanisms complying with IEC/EN
60947-5-1 and capable of switching microloads of 24V DC, 3 mA.

Bulletin 440K, 440G, 440H for interlock switch
Bulletin 440P, 802T for limit switch

Safety sensors

Use approved devices complying with the relevant product standards,
regulations, and rules in the country where used.

Guardmaster products, refer to specific product publications for
details

Relays with forcibly- guided
contacts,
contactors

Use approved devices with forcibly-guided contacts complying with EN 50205. For
feedback purposes, use devices with contacts capable of switching micro loads of
24V DC, 3 mA.

Bulletin 700S, 100S

Other devices

Evaluate whether devices used are appropriate to satisfy the requirements of
safety category levels.

-

ATTENTION: As serious injury may occur due to loss of required safety
function, follow these safety precautions.

Do not use test outputs of the modules as safety outputs.
Do not use DeviceNet standard I/O data or explicit message data as

safety data.

Do not use LED status indicators on the I/O modules for safety

operations.

Do not connect loads beyond the rated value to the safety outputs.
Wire the Guard I/O modules properly so that 24V DC line does not touch

the safety outputs accidentally or unintentionally.

Clear previous configuration data before connecting devices to the

network.

Set unique DeviceNet node addresses before connecting devices to the

network.

Perform testing to confirm that all of the device configuration data and

operation is correct before starting system operation.

When replacing a device, configure the replacement device suitably and

confirm that it operates correctly.

When installing or replacing modules, clear any previous configuration

before connecting input or output power to the device.