For 1791DS-IB4XOW4 modules, follow these instructions on isolating
transformer use. Refer to the isolating transformer figure.

Use an isolating transformer to isolate between over-voltage category III

and II, such as TR1, to conform to IEC 60742.

Be sure the insulation between first input and secondary output satisfies at

least basic insulation of over-voltage category III.

Be sure one side of a secondary output of the isolating transformer is

grounded to prevent electric shock to personnel due to a short to ground
or short to the frame of the isolating transformer.

Insert fuses, in case of a short to the frame, to protect the isolating

transformer and prevent electric shock to personnel, per transformer
specifications, at points such as F1, F2, and F3.

Figure 1 - Use of Isolating Transformer

1791DS-IB4XOW4 Module

L1 L2 L3

400V AC/ 230V AC

III Over-voltage Category II

F1…F8 - Fuses
MA, MB - Electromagnetic Switches
TR1 - Insulated Transformer

44151

F6

F7

F8

F2

F1

TR1

F3

F4

F5

MA

MB

MA

MB

Load