Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

57

Wiring Examples

Chapter 4

Relay Output Examples

Read this section for relay output examples by application. For details, refer to the
installation instructions for each catalog number.

Relay Outputs with Dual-channel Mode and External Device
Monitoring Input

This example shows wiring and controller configuration when using a Guard I/O
module with relay outputs in dual-channel mode and an external device
monitoring input. If used in combination with the programs in a safety
controller, this wiring is Safety Category 4 in accordance with EN 954-1 wiring
requirements.

V0

I0

V1

0

1

G0

E1

E2

F1

F2

AC Supply

K1

K2

T0

G1

C0

31808-M

C1

K1

M

K1

K2

K2

, E2: 24V DC Power Source

, K2: Magnetic Contactors
Three-phase Motor

, F2: Fuses

V0, G0: Input Power Connection
V1, G1: Output Power Connection

Controller
Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Pulse Test Output

Safety Output 0

Safety Output 0 Channel Mode

Safety

Dual-channel Safety Output 0/1 Mode

Dual-channel

Safety Output 1

Safety Output 1 Channel Mode

Safety