Chapter 8

Interpret Status Indicators

Module Status and Network
Status Indicators
Combination

The Module Status (MS) indicator displays the status of a node on the network.
The Network Status (NS) indicator displays the status of the entire network. See
the table for meanings indicated by the combination of colors and status.

State

Status

Description

Recommended Action

Solid green

Normal operation

Safety I/O communication in progress.

None - normal status - safety I/O communication and standard I/O
communication are being performed.

Solid green

Online/connected

Flashing green

Standby

Standard I/O communication or
message communication in progress.

None - normal status - standard I/O communication and/or
message communication are being performed.

Solid green

Online/connected

Flashing green

Standby

Waiting for completion of node address
duplication check at the master.

If this indicator status occurred for only specific module terminals,
check that the module communication rate settings are correct and
restart the module.

Off

Not online or not powered

Flashing green

Standby

Waiting for safety or standard
connection.

None - wait for connection to complete.

Flashing green

Online/not connected

Flashing green/red

Initialization status

Module performing initialization
process or waiting for configuration.

None - wait for process or configuration to complete.

Off

Not online or not powered

Solid red

Fatal fault

Watchdog timer error.

Replace the module.

Off

Not online or not powered

Flashing red

Minor fault

Switch settings are incorrect.

Check the switch settings and restart the module.

Off

Not online or not powered

Flashing green

Standby

Node address duplication.

Reset the module so that it has a unique node address, and then
restart the module.

Solid red

Fatal link fault

Flashing green

Standby

Bus Off status (communication stopped
due to consecutive data errors).

Check the following items and restart the module:

·Do master and module communication rates match?
·Are lengths of cables (trunk and branch lines) correct?
·Are cables broken or loose?
·Are terminating resistors connected to both ends of the trunk
line only?
·Is noise interference excessive?

Solid red

Fatal link fault

Flashing Green

Standby

Communication timeout.

Check the following items and restart the module:

·Do master and module communication rates match?
·Are lengths of cables (trunk and branch lines) correct?
·Are cables broken or loose?
·Are terminating resistors connected to both ends of the trunk
line only?
·Is noise interference excessive?
·Is the network grounded properly ?

Flashing red

Minor communication fault

: Lit

: Flashing

: Not lit

M

NS

MS

NS

MS

NS

MS

NS

MS

NS

MS

NS

MS

NS

MS

NS

MS

NS

MS

NS