Understand the Operation of Safety Functions

Examples to Reduce Noise

These examples show how to reduce noise in 1791DS-IB12, 1791DS-IB8XOB8,
and 1791DS-IB4XOW4 modules.

EXAMPLE

Reduce electrical noise from the communication cable by installing a ferrite
core on the communication cable within 10 cm (3.93 in.) of the DeviceNet
master unit. Use Ferrite Core (Data Line Filter) LF130B, manufactured by
Easy Magnet Co., or an equivalent.

Impedance Specifications

ImpedanceValue

25 MHz

100 MHz

156

Ω

250

Ω

Ferrite Core

EXAMPLE

Wire the control panel with cables that are as short as possible and ground
to 100

Ω or less.

EXAMPLE

Keep DeviceNet communication cables as short as possible and ground to
100

Ω or less.

31522-M

13
(0.51)

29
(1.14)

30
(1.18)

33
(1.30)

Dimensions are in mm (in.).