Interpret Status Indicators

Chapter 8

1732DS-IB8XOBV4,
1732DS-IB8,
1791DS-IB8XOBV4, and
1791DS-IB16 Status
Indicators

Refer to the tables for information on how to interpret status indicators on the
1732DS-IB8XOBV4, 1732DS-IB8, 1791DS-IB8XOB8, and 1791DS-IB16
modules.

Table 10 - Module Status (MS) Indicator

State

Status

Description

Recommended Action

Off

No power or autobauding

No power is applied to the DeviceNet connector.

Apply power to this connector.

Solid green

Normal operation

The module is operating normally.

None.

Solid red

Unrecoverable fault

The module has detected an unrecoverable fault.

Cycle power to the module. If the anomaly persists, replace the
module.

Flashing green

Module needs commissioning
due to missing, incomplete,
or incorrect configuration

Module is unconfigured.

Reconfigure the module. For additional information, inspect the
Network Status (NS) indicator.

Flashing red

Recoverable fault

The module detected a recoverable fault.

Cycle power to the module or reset the module.

User-initiated firmware
update

User-initiated firmware update is in progress.

Wait for the firmware update to complete.

Flashing red and
green

Device in self test

The module is performing its power-cycle diagnostic tests.

Wait for the module to complete its power-cycle diagnostics.

Table 11 - Network Status (NS) Indicator

State

Status

Description

Recommended Action

Off

Module not online or
no power

The module is not online with the network.

Verify your network.

Flashing green

Module online with no
connections in established
state

The module identified the communication rate of the network
but no connections are established.

Verify your network and module configuration.

Solid green

Module online with
connections in established
state

The module is operating normally.

None.

Flashing red

One or more I/O connections
in timed-out state

The module detected a recoverable network fault.

Verify your network and module configuration.

User-initiated firmware
update

User-initiated firmware update is in progress.

Wait for the firmware update to complete.

Solid red

Critical link failure

The module detected an error that prevents it from
communicating on the network.

Cycle power to the module. If the anomaly persists, replace the
module.

Flashing red and
green

Communication faulted
module

The module detected a network access error and is in
communication faulted state. The module has received and
accepted an Identity Communication Faulted Request-long
protocol message.

Verify your network and module configuration.