Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

127

Considerations When Replacing Guard I/O Modules

Chapter 7

If the project is configured for ‘Configure Always’, follow the appropriate steps to
replace a Guard I/O module based on your scenario.

1. Remove the old I/O module and install the new module.

2. Right-click your Guard I/O module and choose Properties.

3. Click the Safety tab.

4. Click Reset Ownership.

5. Click OK.

6. Follow your company-prescribed procedures to functionally test the

replaced I/O module and system and to authorize the system for use.

GuardLogix Project
Safety Signature
Exists

Replacement Module
SNN

Fault

Action Required

Yes or No

Out-of-box

None

None.

Yes or No

Same as original

None

None.

Yes or No

Different from original

SNN mismatch

Click Reset Ownership.
Follow the steps below.