Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 100

Advertising
background image

Publication GMSI10-UM013D-EN-P - May 2010

90 Configuration Parameters

Not 1X and Vector Status (XM
Serial Configuration Utility only)

States whether a fault condition exists on the
associated channel. If a fault exists, the not 1X and
vector measurements may not be accurate.

The following conditions can cause a fault:

a transducer fault on the associated channel

no tachometer signal or a transducer fault exists
on the tachometer channel

the machine speed changes too fast for the
tracking algorithm to keep up or if the frequency of
FMAX goes outside the range of 10 to 5000Hz

Possible status values: No Fault

Fault

Not 1X Value

Shows the magnitude of the vibration excluding the
vibration at the machine speed.

The tachometer must be enabled
(Pulses Per Revolution set to 1 or
more), and a tachometer signal must
be present.

1X Magnitude

The magnitude of the vibration at the machine
speed.

1X Phase

The phase of the vibration at the machine speed.

2X Magnitude

The magnitude of the vibration at two times the
machine speed.

2X Phase

The phase of the vibration at two times the machine
speed.

3X Magnitude

The magnitude of the vibration at three times the
machine speed.

Ch1/Ch2 Spectrum/Waveform
Status (XM Serial Configuration
Utility only)

States whether a fault condition exists on the
associated channel. If a fault exists, the
spectrum/waveform data may not be accurate.

The following conditions can cause a fault:

a transducer fault on the associated channel

Sampling Mode set to "Synchronous" and there
is no tachometer signal or there is a fault on the
tachometer channel

Possible status values: No Fault

Fault

Get Waveform Data Only (XM
Serial Configuration Utility only)

Controls whether the spectrum is calculated by the
Configuration Utility or the Vibration module.

Check to upload only waveform data
from the module. The Configuration
Utility calculates and displays the
spectrum using the collected
waveform data.

Clear to upload both the waveform
and spectrum data from the module.

States whether a fault condition (no tachometer
signal or transducer fault) exists on the tachometer
channel. If a fault exists, the speed value may not be
accurate.

Possible status values: No Fault

Fault

Monitor Data Parameters

Parameter Name

Description

Values/Comments

XM Configuration
Utility

EDS File

Speed Status

Transducer 3
Status

Advertising