Figure 2.29 sho, Figure 2.29, Transducer dc bias is monitored on all signals – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 51: Important

Advertising
background image

Publication GMSI10-UM013D-EN-P - May 2010

Installing the XM-122 gSE Vibration Module 41

Figure 2.29 Velocity Sensor and Two Non-contact Sensor Wiring

IMPORTANT

Transducer DC bias is monitored on all signals.

IMPORTANT

A jumper from terminal 22 to terminal 21 is required for
channel 2 buffered output. Refer to Configuring Buffered
Output Input Range on page 28.

TYPICAL WIRING FOR COIL-BASED VELOCITY SENSOR AND TWO

NON-CONTACT SENSORS TO XM-122 VIBRATION MODULE

Pin A - Common
Pin B - Signal

Cable shield not
connected at this end

Shield

0

16

Channel 1 Input Signal

Signal Common

SIG

-24

COM

SIG

-24

COM

17

1

Signal Common

Channel 2 Input Signal

21

22

-24V DC

20

-24V DC

4

Signal Common

Tach Input Signal

36

13

31

Shield

Shield

*

* Note: Jumpering terminal 22 to
terminal 21 configures
CH 2 buffer (-24V to 9V)

18