Configuration Parameters 61

Channel Signal Processing Parameters

Parameter Name

Description

Values/Comments

Output Data Unit

The data units of the measured values.

The available options depend on the
Eng. Units selection. See page
58.

Very Low HPF Frequency (EDS
File only)

Shows the corner frequency for the Very Low high
pass filter option.

Low HPF Frequency (EDS File
only)

Shows the corner frequency for the Low high pass
filter option.

Medium HPF Frequency (EDS File
only)

Shows the corner frequency for the Medium high
pass filter option.

High HPF Frequency (EDS File
only)

Shows the corner frequency for the High high pass
filter option.

Very High HPF Frequency (EDS
File only)

Shows the corner frequency for the Very High high
pass filter option.

High Pass Filter

Sets the high pass filter to apply to the
measurements. The high pass filter is useful in
removing low frequency signal components that
would dominate the signal. The high pass filter
attenuates all frequencies below a defined
frequency. It allows, or passes, frequencies above
the defined frequency.

Important: Select the Bypass option
when you want a more accurate
representation of dynamic signals at
low frequencies. This option reduces
the distortion of the waveform at low
frequencies and reduces attenuation
at lower frequencies.

Note: The lowest frequency high pass
filter is not available for integrated
measurements.

Eng. Units

Output Data
Unit Options

g

g

ips

mil

mm/sec

um

ips or mm/sec

ips

mil

mm/sec

um

mils or um

mils

um

Volt

volt

Pa or psi

Pa

psi