150 DeviceNet Objects

12

Get/Set

Hysteresis

REAL

The amount on the safe
side of a threshold by
which the value must
recover to clear the alarm.

13

Get/Set

Threshold (Setpoint
Multiplier)

REAL

Indicates how the
thresholds should be
adjusted when the
setpoint multiplication
function is invoked.

0 = Disable alarm
> 0 = Multiply the thresholds by
the value

14

Get/Set

Startup Period

UINT

The amount of time that
the Threshold (Setpoint)
Multiplier is applied after
the startup signal is
received.

Seconds

15

Get/Set

Speed Range
Enable

BOOL

Indicates whether this
alarm is enabled only
within a certain machine
speed range.

0 = No speed range (alarm is
always enabled)
1 = Speed range (alarm only
enabled within speed range)

16

Get/Set

Speed Range High

REAL

Indicates the greater
threshold of the machine
speed range for which the
alarm is enabled (disabled
at greater speeds).

CPM
(must be greater than Speed
Range Low
)

17

Get/Set

Speed Range Low

REAL

Indicates the lesser
threshold of the machine
speed range for which the
alarm is enabled (disabled
at lesser speeds).

CPM
(Must be less than Speed
Range High
)

18

Get/Set

Name

STRING2

A name to help identify
this alarm.

19

Get/Set

Measurement
Identifier

EPATH

Identifies the
measurement object to
which this alarm is
applied.

See Parameter Object instances
10 to 25.

20

Get/Set

Inhibit Tach Fault

BOOL

Determines whether the
Tach Fault status is
prohibited during the
startup period.

0 = Tach Fault allowed
1 = Tach Fault inhibited

Table C.36 Alarm Object Instance Attributes