Publication GMSI10-UM013D-EN-P - May 2010

Wiring Connections for Previous Module Revisions 183

Figure D.3 IEPE Accelerometer to Channel 2 Wiring

Connecting a Non-Contact Sensor

Figures D.4 and D.5 show the wiring of a non-contact sensor to an earlier
revision of the XM-122 module (before revision D01).

TYPICAL WIRING FOR IEPE ACCELEROMETER

TO XM-122 VIBRATION MODULE CHANNEL 2

Shield

Pin A - Signal
Pin B - Common

Cable shield not
connected at this end

1

17

22

6

21

Channel 1 Input Signal

Signal Common

5

38

Jumping terminals
5 to 6 & 21 to 22
configure the
transducer power
supply for IEPE
tranducer(s)

Channel 2 Input Signal

ATTENTION

You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the terminal base
and not at the transducer. Any convenient Chassis terminal
may be used (see Terminal Block Assignments on page
179).

IMPORTANT

The internal transducer power supply is providing power to
the non-contact sensor.