Connecting a passive transducer, Figure 2.20 non-contact sensor to channel 2 wiring, Important – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 42

Advertising
background image

Publication GMSI10-UM013D-EN-P - May 2010

32 Installing the XM-122 gSE Vibration Module

Figure 2.20 Non-contact Sensor to Channel 2 Wiring

Connecting a Passive Transducer

Figures 2.21 and 2.22 show the wiring of a passive transducer, such as a
velocity sensor, to the terminal base unit.

TYPICAL WIRING FOR NON-CONTACT SENSOR

TO XM-122 VIBRATION MODULE CHANNEL 2

COM

SIG

-24

Channel 2 Input Signal

-24V DC

1

17

22

Signal Common

21

Jumper ing terminal 21 to
terminal 22 configures
CH 2 buffer for -24V to +9V

Isolated Sensor Driver

Shield

Shield
Floating

38

ATTENTION

You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the terminal base
and not at the transducer. Any convenient Chassis terminal
may be used (see Terminal Block Assignments on page 18).

IMPORTANT

The module does not power the sensor. It measures only
the input voltage.

Advertising