Transducer object (class id 328h), Class attributes, Instances – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 183: Instance attributes, Class attributes instances instance attributes, Transducer object (class id 328

Advertising
background image

Publication GMSI10-UM013D-EN-P - May 2010

DeviceNet Objects 173

Transducer Object
(Class ID 328

H

)

The Transducer Object models a transducer.

Class Attributes

The Transducer Object provides no class attributes.

Instances

There are 3 instances of this object. Transducer Object instance 1 is for
vibration channel 1. Transducer Object instance 2 is for vibration channel 2,
and Transducer Object instance 3 is for the tachometer channel.

Instance Attributes

Table C.62 Transducer Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

3

Get

DC Bias

REAL

The measured average DC
bias of the transducer
signal in volts.

Volts

4

Get

Status

BOOL

Indicates whether a
transducer fault exists
(the measured DC Bias is
outside the range
specified by Fault High
and Low).

0 = No fault
1 = A transducer fault exists

5

Get/Set

Sensitivity
Value

REAL

Value of the sensitivity of
the transducer in
millivolts per Sensitivity
Units
.

6

Get/Set

Sensitivity Units ENGUNIT

Units of the denominator
of the Sensitivity Value.

See DeviceNet Specification
Volume 1 Appendix K. Also see
Parameter Object instances 1
and 2.

Valid values:
g =1504 hex
in/sec = 2B07 hex
mils = 0800 hex
psi = 1300 hex
volt = 2D00 hex
mm/s = 0900 hex
µm = 2204 hex
Pa = 1309 hex

Advertising