Publication GMSI10-UM013D-EN-P - May 2010

38 Installing the XM-122 gSE Vibration Module

Figure 2.27 IEPE Accelerometer and Non-Contact Sensor Wiring

IMPORTANT

The internal transducer power supply is providing power to
the non-contact sensor.

IMPORTANT

A jumper from terminal 5 to terminal 6 is required for
channel 1 buffered output. A jumper from terminal 22 to
terminal 21 is required for channel 2 buffered output. Refer
to Configuring Buffered Output Input Range on page 28.

TYPICAL WIRING FOR IEPE ACCELEROMETER AND

NON-CONTACT SENSOR TO XM-122 VIBRATION MODULE

Shield

Pin A - Signal
Pin B - Common

Cable shield not
connected at this end

0

16

22

6

21

Channel 1 Input Signal

Signal Common

5

37

SIG

-24

COM

17

1

Signal Common

Channel 2 Input Signal

-24V DC

13

Shield

S hield Floating

Isolated Sensor Driver

*

*

*Note: Jumpering terminal 5 to terminal 6
configures CH 1 buffer (-5V to +24V)

Jumpering terminal 21 to terminal 22
configures CH 2 buffer (-24V to +9V)