108 DeviceNet Information

The Poll response data can also be requested explicitly through Assembly
Object (Class ID 0x4), Instance 101 (0x65) - 106 (0x6A), Data Attribute (3).

The following tables show the static data format of Assembly instances 101–
106.

XM-122 Assembly Instance 101 Data Format

Byte

Definition

0–3

Channel 1 Overall measurement value

4–7

Channel 2 Overall measurement value

8–11

Channel 1 Gap measurement value

12–15

Channel 2 Gap measurement value

16–19

Current Speed measurement value

20–23

Peak Speed measurement value

24–27

Channel 1 Band 1 measurement value

28–31

Channel 2 Band 1 measurement value

32–35

Channel 1 Band 2 measurement value

36–39

Channel 2 Band 2 measurement value

40–43

Channel 1 Band 3 measurement value

44–47

Channel 2 Band 3 measurement value

48–51

Channel 1 Band 4 measurement value

52–55

Channel 2 Band 4 measurement value

56–59

Channel 1 1X Vector Magnitude measurement value

60–63

Channel 1 1X Vector Phase measurement value

64–67

Channel 2 1X Vector Magnitude measurement value

68–71

Channel 2 1X Vector Phase measurement value

72–75

Channel 1 2X Vector Magnitude measurement value

76–79

Channel 1 2X Vector Phase measurement value

80–83

Channel 2 2X Vector Magnitude measurement value

84–87

Channel 2 2X Vector Phase measurement value

88–91

Channel 1 3X Vector Magnitude measurement value

92–95

Channel 2 3X Vector Magnitude measurement value

96–99

Channel 1 Not 1X measurement value

100–103

Channel 2 Not 1X measurement value

104–107

Channel 1 gSE Overall measurement value

108–111

Channel 2 gSE Overall measurement value

112–115

Channel 1 Sum Harmonics measurement value

116–119

Channel 2 Sum Harmonics measurement value

120–123

Acceleration measurement value

Advertising