Gse signal processing parameters, Gse spectrum parameters – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 80

Advertising
background image

Publication GMSI10-UM013D-EN-P - May 2010

70 Configuration Parameters

gSE Signal Processing Parameters

gSE Spectrum Parameters

gSE Signal Processing Parameters

Parameter Name

Description

Values/Comments

gSE Full Scale

The maximum signal level expected to be processed
by the channel for gSE measurements. This value is
used to determine the programmable gain settings
across each stage of the channel’s analog signal
processing circuit.

10 Volt

Important: Most gSE applications are
well matched to the default gSE Full
Scale setting of 10 volts. However, if
gSE levels in excess of 5 gSE are
observed or anticipated, then we
recommended you increase the Full
Scale setting to 50 Volts to better
match the dynamic range for the
application.

Output Data Unit (XM Serial
Configuration Utility only)

The data units of the measured value.

This value is always set to gSE.

High Pass Filter

Sets the high pass filter to apply to the gSE
measurement. The high pass filter is useful in
removing low frequency signal components that
would dominate the signal. The high pass filter
attenuates all frequencies below a defined
frequency. It allows, or passes, frequencies above
the defined frequency.

Options: 200 Hz

500 Hz
1000 Hz
2000 Hz
5000 Hz

gSE Spectrum Parameters

Parameter Name

Description

Values/Comments

FMAX

Sets the maximum frequency for the gSE spectrum
measurement.

10 to 5000 Hz

Number of Lines

The number of lines or bins in the gSE spectrum
measurement. This determines the frequency
resolution of the gSE spectrum measurement.

Options: 100

200
400
800