Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual
Page 109
Advertising
Publication GMSI10-UM013D-EN-P - May 2010
Specifications 99
Alarms
Number
Alarm Parameters
Operators
Hysteresis
Startup Inhibit/Setpoint Multiplication
Speed Inhibit
16 alarm and danger pairs
Any measured parameter
Greater than
Less than
Inside range
Outside range
User configurable in software
Period: 0 to 1092 minutes, adjustable in 0.1
minute increments
Inhibit/multiplication function: Multiply by
N (0 to 10, 0 = Disarm)
A speed range may be specified for each
alarm. When applied, the alarm is disabled
when speed is outside of the defined range.
XM-122 Technical Specifications
Product Feature
Specification