30 Installing the XM-122 gSE Vibration Module

Figure 2.17 IEPE Accelerometer to Channel 1 Wiring

Figure 2.18 IEPE accelerometer to channel 2 wiring

TYPICAL WIRING FOR IEPE ACCELEROMETER

TO XM-122 VIBRATION MODULE CHANNEL 1

Shield

Pin A - Signal
Pin B - Common

Cable shield not
connected at this end

0

16

6

Channel 1 Input Signal

Signal Common

5

37

Jumpering terminal 5
to terminal 6 configures
CH 1 buffer for -5V to +24V

TYPICAL WIRING FOR IEPE ACCELEROMETER

TO XM-122 VIBRATION MODULE CHANNEL 2

Shield

Pin A - Signal
Pin B - Common

Cable shield not
connected at this end

1

17

6

Channel 1 Input Signal

Signal Common

38

Jumpering terminal 6 to
terminal 22 configures
CH 2 buffer for -5V to +24V