Connecting a powered sensor – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual
Page 195
Publication GMSI10-UM013D-EN-P - May 2010
Wiring Connections for Previous Module Revisions 185
Connecting a Powered Sensor
Figures D.6 and D.7 show the wiring of a powered sensor, such as the Model
580 Vibration Pickup, to an earlier version of the XM-122 module (before
D01).
Figure D.6 Powered Sensor to Channel 1 Wiring
ATTENTION
You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the terminal base
and not at the transducer. Any convenient Chassis terminal
may be used (see Terminal Block Assignments on page
179).
0
16
37
+24V DC
Common
Signal
5
6
21
22
Channel 1 Input Signal
Signal Common
Shield
+24V DC
TYPICAL WIRING FOR MODEL 580 VIBRATION PICKUP
TO XM-122 VIBRATION MODULE CHANNEL 1
Cable shield not
connected at this end