192 Guidelines for Setting the Full Scale Value

XM-122 Full Scale Tables

Use the following tables to help you determine the optimal Full Scale value for
the XM-122 module. Refer to the table that corresponds to the units of
vibration that will be used for monitoring.

Table E.1 XM-122 Measuring Acceleration with Accelerometer (100 mV/g)

Max Vibration Level

Full Scale Setting

g’s peak

1Hz HPF

5Hz HPF

10Hz HPF

40Hz HPF

1000Hz HPF

1

0.1

5

0.75

10

1

30

3

40

4

50

5

Table E.2 XM-122 Measuring Velocity with Accelerometer (100 mV/g)

Max Vibration Level

Full Scale Setting

Max High Frequency Peak Amplitude

ips peak mm/s RMS

1Hz HPF

5Hz HPF

10Hz HPF

40Hz HPF

1000Hz HPF

(g pk)

0.3

10

N/A

0.005

0.01

0.03

0.75

4

1

40

N/A

4

3

100

0.009

0.018

0.072

4

10

360

0.085

0.17

0.67

12

30

1000

0.25

0.5

2.2

40

100

3600

0.83

1.66

6.66

120

Table E.3 XM-122 Measuring Displacement with Accelerometer (100 mV/g)

Max Vibration Level

Full Scale Setting

Max High Frequency Peak Amplitude

mils pp micrometers pp

1Hz HPF

5Hz HPF

10Hz HPF 40Hz HPF 1000Hz HPF

(g pk)

10

250

N/A

0.01

0.02

0.07

N/A

4

20

500

0.03

0.06

0.25

30

750

0.04

0.07

0.3

50

1250

0.05

0.09

0.4

Table E.4 XM-122 Measuring Velocity with Velocimeter (100 mV/ips)

Max Vibration Level

Full Scale Setting

ips peak

mm/s RMS

1Hz HPF

5Hz HPF

10Hz HPF

40Hz HPF

1000Hz HPF

3

100

0.75

10

360

1

20

700

2

30

1000

3