72 Configuration Parameters

Tachometer Signal Processing Parameters

Fault Low

The minimum, or most negative, expected DC
voltage from the transducer.

Volts

Note: A voltage reading outside this
range constitutes a transducer fault.

Fault High

The maximum expected DC voltage from the
transducer.

DC Bias Time Constant

The time constant used for exponential averaging
(low pass filtering) of the transducer DC bias
measurement. The corner frequency for the low pass
filter is 1 / (2

π

x DC Bias Time Constant). See

example table below.

Seconds

Tachometer Transducer Parameters

Parameter Name

Description

Values/Comments

Time Constant

(seconds)

-3dB Frequency

(Hz)

Settling Time

(seconds)

1

0.159

2.2

2

0.080

4.4

3

0.053

6.6

4

0.040

8.8

5

0.032

11

6

0.027

13.2

7

0.023

15.4

8

0.020

17.6

9

0.018

19.8

10

0.016

22

IMPORTANT

The tachometer is required for synchronous sampling and
the speed measurement.

If you are not using the tachometer channel, set the Pulses
Per Revolution
to zero. This will disable the tachometer
measurement, and prevent the module from indicating a
tachometer fault.

Tachometer Signal Processing Parameters

Parameter Name

Description

Values/Comments

Pulses Per Revolution

The number of tachometer signal pulses per
revolution of the shaft (number of gear teeth). This
setting is useful if a proximity probe located over a
gear or shaft with a multi-toothed speed sensing
surface is used to generate the input signal.

Enter zero if you are not using the
tachometer channel to disable the
tachometer measurement.