Instance attributes, Services, Instance attributes services – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 182

Advertising
background image

Publication GMSI10-UM013D-EN-P - May 2010

172 DeviceNet Objects

Instance Attributes

Services

1

Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.

Table C.60 Tachometer Channel Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

3

Get/Set

Number of
Pulses per
Revolution

UINT

The number of signal
pulses per revolution of
the shaft (number of gear
teeth).

0 = Tachometer disabled
> 0 = Tachometer enabled

4

Get/Set

Auto Trigger

BOOL

Indicates whether the
trigger level is determined
automatically from the
signal.

0 = Use specified Trigger Level
and Hysteresis
1 = Determine trigger level and
hysteresis automatically

5

Get/Set

Trigger Level

REAL

The signal level to be
used as the trigger.

Volts

6

Get/Set

Trigger Slope

USINT

The slope of the signal at
the threshold crossing to
be used as the trigger.

0 = Positive
1 = Negative

7

Get/Set

Trigger
Hysteresis

REAL

The amount of hysteresis
around the trigger level.

In Auto Trigger mode, this
value is a percentage of the
peak-to-peak input signal and
can range from 0 to 50%. In
Manual Trigger mode, this
value is a voltage level (the
hysteresis voltage is added or
subtracted to the threshold
voltage to determine the
hysteresis range).

8

Get/Set

Name

STRING2

A name to help identify
this channel.

18 characters maximum

10

Get/Set

Fault Time-out

USINT

Number of seconds with
no pulses before a Tach
Fault is indicated.

1 to 64 seconds

Table C.61 Tachometer Channel Object Services

Service
Code

Class/Instance Usage

Name

Description

0E

h

Instance

Get_Attribute_Single

Returns a single attribute.

10

h

Instance

Set_Attribute_Single

Sets a single attribute.